The life and efficiency of a heating or cooling system is greatly dependent on the quality of the system water. Air and dirt problems cause frequent breakdowns and a huge increase in customer complaints. Corrosion, cavitation and component wear are consequences of air-saturated, dirty system water. Recurring problems and increased maintenance results in unnecessary costs and dissatisfied customers. There is a solution...
A system without air is possible. There is a unique dual-purpose device that will remove air and dirt – down to the smallest particles – keeping the system free from air and dirt, permanently. It works differently to traditional filters, with less maintenance and fewer costs.
An air- and dirt-free water system through one unit. Solves problems arising with air and dirt in water systems.
Deaeration describes the removal of dissolved gases from liquids such as air from water. When water is heated or the pressure is reduced, gas microbubbles are released into the system. Microbubbles can be the cause of major problems such as pump failure, corrosion and energy loss.
The Supaflex SCAD combines the removal of air and dirt through a single unit. Installed at the hottest point in the system the unit will eliminate these microbubbles from heating and chilled water systems.
Microbubbles are mostly released when system temperature is highest based on Henry's Law. Henry's Law states that air is released from water as the temperature increases or the pressure decreases. For this reason, the Microbubble deaerators and dirt separators are typically installed
Chilled Water System
Heating System
Model | Size | H (mm) | h (mm) | d (BSP) | D (mm) | L (mm) | Flow Rate (m³/h) | Weight (kg) |
SCAD-DN20 | 20 | 265 | 112 | ¾" | Φ 65 | 100 | 1.25 | 1.7 |
SCAD-DN25 | 25 | 265 | 112 | 1" | Φ 65 | 100 | 2 | 1.7 |
SCAD-DN40 | 40 | 265 | 112 | 1½" | Φ 65 | 100 | 5 | 1.7 |
SCAD-DN50 | 50 | 332 | 137 | 2" | Φ 88 | 134 | 8 | 6 |
The Supaflex SCAD is also used to remove dirt particles from heating and chilled water systems. When installed it will eliminate all dirt particles down to 10 microns
This unit must be installed at the hottest part of the system. In a heating system this is the main flow from the boilers. The static head must not exceed 15 metres. In a chilled water system the unit must be located in the return, close to the chiller. Maximum static head must not exceed 10 metres.
N.B. If the static head is greater than these figures the efficiency of the unit is reduced. The maximum flow velocity through the unit is 3m/s. If these values are exceeded the efficiency is reduced.
The Supaflex SCAD requires no special commissioning. Maintenance will be required to remove trapped dirt and sludge; this is done by opening the ball valve at the bottom of the unit. The valve may be opened while the system is under pressure. Scalding is a danger at high pressures and temperatures. Ensure that the water is safely piped to a drain before opening the valve.
The system pressure will flush the dirt out – leave the valve open until the collected dirt has been flushed out and repeat this operation every few days. Once the water is clear, it may be possible to drain every six months or so, depending on the size and age of the system. Most of the dissolved air will be removed in a few days.
However this may vary from system to system. In large systems it may take several weeks. Dirt separators can only remove dirt that is circulating.
All models are supplied with a ball valve for draining the collected dirt and sludge.
Supaflex also supply larger flanged units (50-600mm) both combined or as separate air and dirt separators. They can also be removable/demountable and magnetic. We also offer consultation on hydronic separators and vacuum degasser units with dirt separators (for high static heads only).